C1 series hall effect current sensor is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.
Electrical data (Ta=25ºC±5ºC,RL=2KΩ,CL=10000PF) |
Type |
C1-100A |
C1-200A |
C1-300A |
C1-400A |
C1-500A |
Unit |
Rated current(Ipn) |
±100 |
±200 |
±300 |
±400 |
±500 |
A |
Measure range(Ip) |
0-±200 |
0-±400 |
0-±600 |
0-±800 |
0-±1000 |
A |
Rated output |
@Ip=±Ipn ±4±1% |
V |
Supply voltage |
±12,±15 |
V |
Power Consumption |
<25 |
mA |
Offset voltage |
@Ip=0 ±20 |
mV |
Magnetic offset |
@Ip=±Ipn-0 ±20 |
mV |
Offset drift |
@ -40~+85ºC ≤±1 |
mV/ºC |
Output drift |
@ -40~+85ºC ≤±1 |
mV/ºC |
Linearity |
@Ip=0-±Ipn ≤1 |
%FS |
Response time |
@50A/μS, 10%-90% ≤5 |
μs |
Galvanic isolation |
@ 50HZ,AC,1min 2.5 |
KV |
Isolation resistance |
@ DC 500V 1000 |
MΩ |
·Variable speed drives
·Welding machine
·Battery supplied applications
·Uninterruptible Power Supplies (UPS)
·Electrochemical
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
3. Elucidation: 1:+15V 2:-15V 3:V0UT 4:0V
1. When the current will be measured goes through a sensor, the voltage will be measured at the output end.(Note: The false wiring may result in the damage of the sensor)
2. Custom design in the different rated input current and the output voltage are available.
·UL94-V0.
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
|
Value |
Unit |
Operating temperature(TA) |
-40 to +85 |
ºC |
Storage temperature(TS) |
-40 to +125 |
ºC |
Mass(approx) (M) |
62 |
g |